List of Parameters
Parameters
1-65
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Selects function of digital input 0.
Values: 0: Digital input disabled
1: ON/OFF1
2: ON reverse /OFF1
3: OFF2 - coast to standstill
4: OFF3 - quick ramp-down
9: Fault acknowledge
10: JOG right
11: JOG left
12: Reverse
13: MOP up (increase frequency)
14: MOP down (decrease frequency)
15: Fixed frequency selector bit0
16: Fixed frequency selector bit1
17: Fixed frequency selector bit2
18: Fixed frequency selector bit3
27: Enable PID
29: External trip
33: Disable additional freq setpoint
99: Enable BICO parameterization
Dependency: Setting 99 (enable BICO parameterization) requires:
P0700 command source or
P0010 = 1, P3900 = 1, 2 or 3 (quick commissioning) or
P0010 = 30, P0970 = 1 factory reset in order to reset
Note: "ON/OFF1" can only be selected for one digital input (e.g. P0700 = 2 and P0701 = 1).
Configuring DI1 with P0702 = 1 will disable DI0 by setting P0701 = 0. Only the last activated digital input serves as
a command source.
"ON/OFF1" on a digital input can be combined with "ON reverse/OFF1" on another digital input.
p0701[0...2] Function of digital input 0 / Function of DI0
CU240E
CU240S
PM250, PM260
Access level: 2 P-Group: Commands Data type: Unsigned16
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
0 99 1