Parameters
List of Parameters
1-126
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Sets jog ramp-up time.
This is the time used while jogging is active.
Notice: Ramp times will be used as follows:
P1060 / P1061 : JOG mode is active
P1120 / P1121 : Normal mode (ON/OFF) is active
P1060 / P1061 : Normal mode (ON/OFF) and P1124 is active
The rounding of P1130 - P1133 also applies to the JOG ramping.
Description: Sets ramp-down time.
This is the time used while jogging is active.
Notice: Ramp times will be used as follows:
P1060 / P1061 : JOG mode is active
P1120 / P1121 : Normal mode (ON/OFF) is active
P1060 / P1061 : Normal mode (ON/OFF) and P1124 is active
Description: Defines source of main setpoint.
Description: Defines source of main setpoint.
Description: Defines source of the main setpoint scaling.
p1060[0...2] JOG ramp-up time / JOG ramp-up time
Access level: 2 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: NO Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.00 [s] 650.00 [s] 10.00 [s]
p1061[0...2] JOG ramp-down time / JOG ramp-down time
Access level: 2 P-Group: Setpoints Data type: Floating Point
Quick comm. NO Active: NO Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.00 [s] 650.00 [s] 10.00 [s]
p1070[0...2] CI: Main setpoint / Main setpoint
CU240E
CU240S
Access level: 3 P-Group: Setpoints Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 755[0]
p1070[0...2] CI: Main setpoint / Main setpoint
CU240S DP
CU240S DP-F
CU240S PN
Access level: 3 P-Group: Setpoints Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 2050[1]
p1071[0...2] CI: Main setpoint scaling / Main setp scal
Access level: 3 P-Group: Setpoints Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 1