List of Parameters
Parameters
1-77
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Selects function of digital input AI0 (via analog input)
Values: 0: Digital input disabled
1: ON/OFF1
2: ON reverse /OFF1
3: OFF2 - coast to standstill
4: OFF3 - quick ramp-down
9: Fault acknowledge
10: JOG right
11: JOG left
12: Reverse
13: MOP up (increase frequency)
14: MOP down (decrease frequency)
15: Fixed frequency selector bit0
16: Fixed frequency selector bit1
17: Fixed frequency selector bit2
18: Fixed frequency selector bit3
27: Enable PID
29: External trip
33: Disable additional freq setpoint
99: Enable BICO parameterization
Note: See P0701 (function of digital input 0). Signals above 4 V are active, signals below 1,6 V are inactive.
Description: Selects function of digital input AI1 (via analog input)
Values: 0: Digital input disabled
1: ON/OFF1
2: ON reverse /OFF1
3: OFF2 - coast to standstill
4: OFF3 - quick ramp-down
9: Fault acknowledge
10: JOG right
11: JOG left
12: Reverse
13: MOP up (increase frequency)
14: MOP down (decrease frequency)
15: Fixed frequency selector bit0
16: Fixed frequency selector bit1
17: Fixed frequency selector bit2
18: Fixed frequency selector bit3
25: DC brake enable
27: Enable PID
29: External trip
33: Disable additional freq setpoint
99: Enable BICO parameterization
Note: See P0701 (function of digital input 0).
Signals above 4 V are active, signals below 1,6 V are inactive.
p0712[0...2] Analog / digital input 0 / Ana/digi input 0
PM250
PM260
Access level: 2 P-Group: Commands Data type: Unsigned16
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
0 99 0
p0713[0...2] Analog / digital input 1 / Ana/digi input 1
PM240 Access level: 2 P-Group: Commands Data type: Unsigned16
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
0 99 0