Siemens Sinamics G120 Series - p0840[0...2] BI: ON;OFF1; ON;OFF1

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-96
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Allows ON/OFF1 command source to be selected using BICO.
Dependency: For digital inputs as command source BICO requires P0700 set to 2 (enable BICO).
The default setting (ON right) is digital input 0 (722.0).
Alternative source possible only when function of digital input 0 is changed (via P0701) before changing value of
P0840.
When Standard Telegram selected (p0700 = 6, p0922 = Standard Telegram), parameter cannot be changed.
Description: Allows ON/OFF1 command source to be selected using BICO.
Dependency: For digital inputs as command source BICO requires P0700 set to 2 (enable BICO).
The default setting (ON right) is digital input 0 (722.0).
Alternative source possible only when function of digital input 0 is changed (via P0701) before changing value of
P0840.
When Standard Telegram selected (p0700 = 6, p0922 = Standard Telegram), parameter cannot be changed.
Description: Allows ON/OFF1 command source to be selected using BICO.
Dependency: For digital inputs as command source BICO requires P0700 set to 2 (enable BICO).
The default setting (ON right) is digital input 0 (722.0).
Alternative source possible only when function of digital input 0 is changed (via P0701) before changing value of
P0840.
When Standard Telegram selected (p0700 = 6, p0922 = Standard Telegram), parameter cannot be changed.
Description: Allows ON/OFF1 command source to be selected using BICO.
Dependency: When Standard Telegram selected (p0700 = 6, p0922 = Standard Telegram), parameter cannot be changed.
p0840[0...2] BI: ON/OFF1 / ON/OFF1
CU240E
CU240S
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 722.0
p0840[0...2] BI: ON/OFF1 / ON/OFF1
CU240S DP Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 2090.0
p0840[0...2] BI: ON/OFF1 / ON/OFF1
CU240S PN Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 8890.0
p0840[0...2] BI: ON/OFF1 / ON/OFF1
CU240S DP-F Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 2090.0