EasyManua.ls Logo

Siemens Sinamics G120 Series - r2032.0...15 BO: CtrlWrd1 from USS on RS232; CtrlWd1 <- USS; r2033.0...15 BO: CtrlWrd2 from USS on RS232; CtrlWd2 <- USS

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-208
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Displays control word 1 from USS on RS232 (word 1 within USS).
Description: Displays control word 2 from USS on RS232 (i.e. word 4 within USS).
Dependency: P0700 = 4 (USS on RS232) and P0719 = 0 (Cmd / Setpoint = BICO parameter).
Description: Displays control word 2 from USS on RS232 (i.e. word 4 within USS).
Dependency: P0700 = 4 (USS on RS232) and P0719 = 0 (Cmd / Setpoint = BICO parameter).
r2032.0...15 BO: CtrlWrd1 from USS on RS232 / CtrlWd1 <- USS
Access level: 3 P-Group: Communications Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OFF2: Electrical stop No Yes -
02 OFF3: Fast stop No Yes -
03 Pulse enable Yes No -
04 RFG enable Yes No -
05 RFG start Yes No -
06 Setpoint enable Yes No -
07 Fault acknowledge Yes No -
08 JOG right Yes No -
09 JOG left Yes No -
10 Control from PLC Yes No -
11 Reverse (setpoint inversion) Yes No -
13 Motor potentiometer MOP up Yes No -
14 Motor potentiometer MOP down Yes No -
15 CDS Bit 0 (Hand/Auto) Yes No -
r2033.0...15 BO: CtrlWrd2 from USS on RS232 / CtrlWd2 <- USS
PM240 Access level: 3 P-Group: Communications Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fixed frequency Bit 0 Yes No -
01 Fixed frequency Bit 1 Yes No -
02 Fixed frequency Bit 2 Yes No -
03 Fixed frequency Bit 3 Yes No -
04 Drive Dataset (DDS) Bit 0 Yes No -
05 Drive Dataset (DDS) Bit 1 Yes No -
08 Enable PID Yes No -
09 Enable DC brake Yes No -
11 Enable Droop Yes No -
12 Torque control Yes No -
13 External fault 1 No Yes -
15 Command Dataset (CDS) Bit 1 Yes No -
r2033.0...15 BO: CtrlWrd2 from USS on RS232 / CtrlWd2 <- USS
PM250
PM260
Access level: 3 P-Group: Communications Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fixed frequency Bit 0 Yes No -
01 Fixed frequency Bit 1 Yes No -
02 Fixed frequency Bit 2 Yes No -
03 Fixed frequency Bit 3 Yes No -
04 Drive Dataset (DDS) Bit 0 Yes No -
05 Drive Dataset (DDS) Bit 1 Yes No -
08 Enable PID Yes No -
11 Enable Droop Yes No -
12 Torque control Yes No -
13 External fault 1 No Yes -
15 Command Dataset (CDS) Bit 1 Yes No -