EasyManua.ls Logo

Siemens Sinamics G120 Series - p0719[0...2] Selection of cmd. & freq. setp.; Cmd.&freq.setp.sel

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-80
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Central switch to select control command source for inverter.
Switches command and setpoint source between freely programmable BICO parameters and fixed command/set-
point profiles.
Command and setpoint sources can be changed independently.
The tens digit chooses the command source and the units digit chooses the setpoint source.
Values: 0: Cmd = BICO parameter Setpoint = BICO parameter
1: Cmd = BICO parameter Setpoint = MOP setpoint
2: Cmd = BICO parameter Setpoint = Analog setpoint
3: Cmd = BICO parameter Setpoint = Fixed frequency
4: Cmd = BICO parameter Setpoint = USS on RS232
6: Cmd = BICO parameter Setpoint = Fieldbus
7: Cmd = BICO parameter Setpoint = Analog setpoint 2
10: Cmd = BOP Setpoint = BICO parameter
11: Cmd = BOP Setpoint = MOP setpoint
12: Cmd = BOP Setpoint = Analog setpoint
13: Cmd = BOP Setpoint = Fixed frequency
14: Cmd = BOP Setpoint = USS on RS232
16: Cmd = BOP Setpoint = Fieldbus
17: Cmd = BOP Setpoint = Analog setpoint 2
40: Cmd = USS on RS232 Setpoint = BICO parameter
41: Cmd = USS on RS232 Setpoint = MOP setpoint
42: Cmd = USS on RS232 Setpoint = Analog setpoint
43: Cmd = USS on RS232 Setpoint = Fixed frequency
44: Cmd = USS on RS232 Setpoint = USS on RS232
46: Cmd = USS on RS232 Setpoint = Fieldbus
47: Cmd = USS on RS232 Setpoint = Analog setpoint 2
60: Cmd = Fieldbus Setpoint = BICO parameter
61: Cmd = Fieldbus Setpoint = MOP setpoint
62: Cmd = Fieldbus Setpoint = Analog setpoint
63: Cmd = Fieldbus Setpoint = Fixed frequency
64: Cmd = Fieldbus Setpoint = USS on RS232
66: Cmd = Fieldbus Setpoint = Fieldbus
67: Cmd = Fieldbus Setpoint = Analog setpoint 2
Dependency: P0719 has higher priority than P0700 and P1000.
If set to a value other than 0 (i.e. BICO parameter is not the setpoint source), P0844 / P0848 (first source of OFF2 /
OFF3) are not effective; instead, P0845 / P0849 (second source of OFF2 / OFF3) apply and the OFF commands
are obtained via the particular source defined.
BICO connections made previously remain unchanged.
USS on RS485 is not supported.
Notice: Particularly useful when e.g. changing command source temporarily from P0700 = 2.
Settings in P0719 (contrary to P0700 settings) do not reset the digital inputs (P0701, P0702, ...)
p0719[0...2] Selection of cmd. & freq. setp. / Cmd.&freq.setp.sel
CU240S DP
CU240S DP-F
CU240S PN
Access level: 4 P-Group: Commands Data type: Unsigned16
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
0 67 0

Table of Contents

Related product manuals