List of Parameters
Parameters
1-165
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Configuration for speed control.
Note: P1400 Bit 00 = 1:
Automatic gain adaption of speed controller (P1460 resp. P1470) is enabled. In the area of field weakening the gain
is reduced in dependence on flux.
P1400 Bit01 = 1:
The integrator of the speed controller is frozen if Sensorless Vector Control (SLVC) is selected and the control is
switched from closed-loop to open-loop operation.
Advantage:
The correct amount of slip compensation is calculated and applied to the open-loop function for a motor under load.
Description: Displays status of motor control, which can be used to diagnose inverter status.
Note: See P0052 (CO/BO: Status word 1)
Description: Displays setpoint of speed controller.
Description: Sets time constant of PT1 filter to smooth actual speed of speed controller.
p1400[0...2] Configuration of speed control / Config. of n-ctrl.
Access level: 3 P-Group: Closed-loop control Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
- - 0001 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Automatic Kp adaption Yes No -
01 Integral freeze (SLVC) Yes No -
r1407.0...15 CO/BO: Status 2 of motor control / Stat 2 ctrl
Access level: 3 P-Group: Closed-loop control Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 V/f control enabled Yes No -
01 SLVC enabled Yes No -
02 Torque control enabled Yes No -
05 Stop I-comp. speed control Yes No -
06 Set I-comp. speed controller Yes No -
08 Upper torque limit active Yes No -
09 Lower torque limit active Yes No -
10 Droop active Yes No -
15 DDS change active Yes No -
r1438 CO: Freq. setpoint to controller / Freq. setp ctl
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [Hz] Data set: -
p1442[0...2] Filter time for act. speed / Filter time n_act.
CU240S
CU240S DP
CU240S DP-F
CU240S PN
Access level: 2 P-Group: Closed-loop control Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
2 [ms] 32000 [ms] 2 [ms]