Siemens Sinamics G120 Series - p2042 Selection of ident number; Ident nb; r2050[0...7] CO: PZD from Fieldbus; PZD from FB

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-211
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Selects if native ident number (0) or NAMUR ident number (1) is send to the PLC.
Values: 0: Native
1: Namur
Note: After changing P2042, a power cycle must be done to have changes take effect.
See also : Switching to / from Namur in the description of parameter P0922.
Description: Displays PZD received from Fieldbus.
Index: [0] = Received word 0
[1] = Received word 1
[2] = Received word 2
[3] = Received word 3
[4] = Received word 4
[5] = Received word 5
[6] = Received word 6
[7] = Received word 7
Note: The control words can be viewed as bit parameters r2090 and r2091.
p2042 Selection of ident number / Ident nb
Access level: 3 P-Group: - Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: T
Min Max Factory setting
0 1 0
r2050[0...7] CO: PZD from Fieldbus / PZD from FB
CU240S DP
CU240S DP-F
CU240S PN
Access level: 3 P-Group: Communications Data type: Unsigned16
Unit: - Data set: -
r2090
[0]
r2050
[1]
[2]
[3]
PZD1
STW1
PZD2PZD3PZD4
PZD
STW
HSW
Fieldbus
PZD mapping to parameter r2050
Process data
Control word
Main setpoint
...
[7]
depends on setting in P0922
...