EasyManua.ls Logo

Siemens Sinamics G120 Series - r0747.0...2 CO;BO: State of digital outputs; CO;BO:State DOs; p0748 Invert digital outputs; Invert DOs; r0750 Number of AIs; Number of AIs; r0751.0...9 CO;BO: Status word of AI; AI status Wd

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-84
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Displays status of digital outputs (also includes inversion of digital outputs via P0748).
Dependency: Bit = 0 signal: Contacts open
Bit = 1 signal: Contacts closed
Description: Defines high and low states of relay for a given function.
Description: Displays number of analog inputs available.
Description: Displays status of analog input.
Description: Displays smoothed analog input value in volts or milliamps before the scaling block.
Index: [0] = Analog input 0 (AI0)
[1] = Analog input 1 (AI1)
r0747.0...2 CO/BO: State of digital outputs / CO/BO:State DOs
Access level: 3 P-Group: Commands Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Digital output 0 energized Yes No -
01 Digital output 1 energized Yes No -
02 Digital output 2 energized Yes No -
p0748 Invert digital outputs / Invert DOs
Access level: 3 P-Group: Commands Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: U, T
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Invert digital output 0 Yes No -
01 Invert digital output 1 Yes No -
02 Invert digital output 2 Yes No -
r0750 Number of AIs / Number of AIs
Access level: 3 P-Group: Terminals Data type: Unsigned16
Unit: - Data set: -
r0751.0...9 CO/BO: Status word of AI / AI status Wd
Access level: 3 P-Group: Terminals Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Signal lost on AI0 Yes No -
01 Signal lost on AI1 Yes No -
08 No signal lost on AI0 Yes No -
09 No signal lost on AI1 Yes No -
r0752[0...1] Act. input of AI [V] or [mA] / Act.AI inp.[V/mA]
Access level: 2 P-Group: Terminals Data type: Floating Point
Unit: - Data set: -