EasyManuals Logo

Siemens Sinamics G120 Series User Manual

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #160 background imageLoading...
Page #160 background image
Parameters
List of Parameters
1-160
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Sets V/f coordinates (P1320/1321 to P1324/1325) to define V/f characteristic.
These parameter pairs can be used to provide correct torque at correct frequency and is useful when used with
synchronous motors. Parameter P1320 defines the frequency of the first point of the characteristic.
Dependency: To set parameter, select P1300 = 3 (V/f with programmable characteristic).
The acceleration boost and starting boost defined in P1311 and P1312 are applied to V/f with programmable char-
acteristic.
Note: Linear interpolation will be applied between the individual data points.
V/f with programmable characteristic (P1300 = 3) has 3 programmable points and 2 non-programmable points.
The 2 non-programmable points are:
Continuous boost P1310 at 0 Hz
Rated motor voltage P0304 at rated motor frequency P0310
Description: See P1320 (programmable V/f freq. coord. 1).
Description: See P1320 (programmable V/f freq. coord. 1).
Description: See P1320 (programmable V/f freq. coord. 1).
Description: See P1320 (programmable V/f freq. coord. 1).
p1320[0...2] Programmable V/f freq. coord. 1 / V/f freq. coord. 1
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: T
Min Max Factory setting
0.00 [Hz] 650.00 [Hz] 0.00 [Hz]
p1321[0...2] Programmable V/f volt. coord. 1 / V/f volt. coord. 1
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.0 [V] 3000.0 [V] 0.0 [V]
p1322[0...2] Programmable V/f freq. coord. 2 / V/f freq. coord. 2
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: T
Min Max Factory setting
0.00 [Hz] 650.00 [Hz] 0.00 [Hz]
p1323[0...2] Programmable V/f volt. coord. 2 / V/f volt. coord. 2
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.0 [V] 3000.0 [V] 0.0 [V]
p1324[0...2] Programmable V/f freq. coord. 3 / V/f freq. coord. 3
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: T
Min Max Factory setting
0.00 [Hz] 650.00 [Hz] 0.00 [Hz]

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Sinamics G120 Series and is the answer not in the manual?

Siemens Sinamics G120 Series Specifications

General IconGeneral
SeriesSinamics G120
Protection ClassIP20
Communication InterfacesPROFIBUS, PROFINET, USS, Modbus RTU
Safety IntegratedSTO
Power Supply24 V DC
Ambient Temperature-10 to +50 °C (depending on the specific model)
Power Rating0.37 kW to 250 kW
Storage Temperature Range+70 °C
Relative Humidity5% to 95% (non-condensing)

Related product manuals