Siemens Sinamics G120 Series - Fig. 2-24 4160 - Control word 2 (r0055)

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function diagrams
Technology Functions
2-346
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Fig. 2-24 4160 – Control word 2 (r0055)
- 4160 -
Function diagram
87654321
4160_STW2.vsd
Technology Functions
SINAMICS G120
02.04.2007 V3.0
Control word 2 (r0055)
1)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
The sequence control is the internal
control (software) for realizing the
inverter status (r0001)
Bit No. Meaning
0 = NO
1 = Fixed frequency Bit 0
0 = NO
1 = Fixed frequency Bit 1
0 = NO
1 = Fixed frequency Bit 2
0 = NO
1 = Fixed frequency Bit 3
0 = NO
1 = Drive data set (DDS) Bit 0
0 = NO
1 = Drive data set (DDS) Bit 1
reserved
reserved
0 = NO
1 = PID enable
0 = NO
1 = DC brake enable
reserved
0 = NO
1 = Droop enable (only SLVC/VC)
0 = NO
1 = Torque control (only SLVC/VC)
0 = External fault 1
1 = No external fault
reserved
0 = NO
1 = Command data set (CDS) Bit 1
Act CtrlWd2
r0055
r0055
Parameter r0055
(722.3)
FF sel. Bit 0 P1020.CDS
(722.4)
FF sel. Bit 1 P1021.CDS
(722.5)
FF sel. Bit 2
P1022.CDS
(722.6)
FF sel. Bit 3 P1023.CDS
(0)
DDS bit 0 P0820
(0)
DDS bit 1
P0821
(0)
Enab. PID ctrl P2200.CDS
(0)
Enable DC brk.
P1230.CDS
(0)
BI:-> torque ctrl.
P1501.CDS
(1)
External fault
P2106.CDS
(0)
CDS bit 1 P0811
(722.0)
ON/OFF1
P0840.CDS
(0)
BI:ON reverse/OFF1
P0842.CDS
Droop input source
0 ... 3
P1488.DDS (0)
Sequence control 1)
Sequence control 1)
Speed control
DC braking control
PID control
Sequence control 1)
Fixed frequencies
Speed/torque control
Fixed frequencies
Fixed frequencies
Fixed frequencies
Sequence control 1)
1 0 3 2 5 47 6
9 8
11 10 13 12 15 14
Segment Bit
Segment Bit
Seven-segment display
(0)
Enable droop
P1492.CDS