List of Parameters
Parameters
1-53
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Specifies second magnetizing current value of saturation characteristic in [%] relative to rated magnetizing current
(P0331).
The saturation characteristic is defined using 4 points (P0362 - P0365, P0366 - P0369). This parameter specifies
the x coordinate (magnetizing current) for the second value pair of the characteristic.
Dependency: Affects P0320 (motor magnetizing current).
The following applies for the magnetizing currents: P0366 < P0367 < P0368 < P0369, otherwise a linear character-
istic is applied internally.
Description: Specifies third magnetizing current value of saturation characteristic in [%] relative to rated magnetizing current
(P0331).
The saturation characteristic is defined using 4 points (P0362 - P0365, P0366 - P0369). This parameter specifies
the x coordinate (magnetizing current) for the third value pair of the characteristic.
Dependency: Affects P0320 (motor magnetizing current).
The following applies for the magnetizing currents: P0366 < P0367 < P0368 < P0369, otherwise a linear character-
istic is applied internally.
Description: Specifies fourth magnetizing current value of saturation characteristic in [%] relative to rated magnetizing current
(P0331).
The saturation characteristic is defined using 4 points (P0362 - P0365, P0366 - P0369). This parameter specifies
the x coordinate (magnetizing current) for the fourth value pair of the characteristic.
Dependency: Affects P0320 (motor magnetizing current).
The following applies for the magnetizing currents: P0366 < P0367 < P0368 < P0369, otherwise a linear character-
istic is applied internally.
Description: Displays standardized stator resistance of motor equivalent circuit (phase value) in [%].
p0367[0...2] Magnetizing curve imag 2 / Magnet.curve imag2
Access level: 4 P-Group: Motor Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
20.0 [%] 250.0 [%] 75.0 [%]
p0368[0...2] Magnetizing curve imag 3 / Magnet.curve imag3
Access level: 4 P-Group: Motor Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
20.0 [%] 250.0 [%] 135.0 [%]
p0369[0...2] Magnetizing curve imag 4 / Magnet.curve imag4
Access level: 4 P-Group: Motor Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
20.0 [%] 250.0 [%] 170.0 [%]
r0370[0...2] Stator resistance [%] / Stator res. [%]
Access level: 4 P-Group: Motor Data type: Floating Point
Unit: [%] Data set: DDS

Table of Contents