F00453 Motor Stalled
Reaction: OFF 2
Acknowledge: Quit fault eg. via DI2
Cause: In SLVC or VC (p1300 greater than 20) and Ramp rate too fast
In SLVC or VC (p1300 greater than 20) and done OFF2 and RUN onto a spinning motor without Flying start
enabled
In SLVC (p1300 = 20 or 21) and load too large at very low frequency
In SLVC or VC (p1300 greater than 20) and no motor connected or motor too small for inverter
In VC, the motor cable phase sequence (U-V-W) and the encoder cable wiring may be wired up incorrectly.
The speed controller settings are not optimised to the application. This can cause instabilities.
Remedy: Reduce ramp rate in p1120
Enable flying start (p1200 equal to 1)
Increase boost in p1611
Connect motor or use larger motor for this inverter or use VF mode (p1300 less than 20).
Correct the wiring to the motor and / or the encoder as required. Confirm the rotation direction in V/f control
mode and compare parameters r0061 and r0021.
Optimise the speed controller settings (gain and integration time).
A00501 Current Limit
Reaction: NONE
Acknowledge: NONE
Cause: Motor power does not correspond to the inverter power
Motor leads are too long
Earth faults
Remedy: Check the following:
Motor power (P0307) must correspond to inverter power (r0206).
Cable length limits must not be exceeded.
Motor cable and motor must have no short-circuits or earth faults
Motor parameters must match the motor in use
Value of stator resistance (P0350) must be correct
Motor must not be obstructed or overloaded
Increase Ramp-up time (P1120)
Reduce Starting boost level (P1312)
A00502 Overvoltage limit
Reaction: NONE
Acknowledge: NONE
Cause: Overvoltage limit is reached. This warning can occur during ramp down, if the Vdc controller is disabled (P1240 = 0).
Remedy: If this warning is displayed permanently, check drive input voltage.
A00503 UnderVoltage Limit
Reaction: NONE
Acknowledge: NONE
Cause: Main supply failed
Main supply and consequently DC-link voltage (r0026) below specified limit.
Remedy: Check main supply voltage.