EasyManua.ls Logo

Siemens Sinamics G120 Series - p2221[0...2] BI: Fixed PID setp. select Bit 1; BI:PID setp->Bit 1; p2222[0...2] BI: Fixed PID setp. select Bit 2; BI:PID setp->Bit 2; p2223[0...2] BI: Fixed PID setp. select Bit 3; BI:PID setp->Bit 3; r2224 CO: Act. fixed PID setpoint; Fixed.PID setp

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-241
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Defines command source of fixed PID setpoint selection Bit 1.
Description: Defines command source of fixed PID setpoint selection Bit 2.
Description: Defines command source of fixed PID setpoint selection Bit 3.
Description: Defines command source of fixed PID setpoint selection Bit 3.
Description: Displays total output of PID fixed setpoint selection.
Note: R2224 = 100 % corresponds to 4000 hex.
Description: Displays the status of PID fixed frequencies.
p2221[0...2] BI: Fixed PID setp. select Bit 1 / BI:PID setp->Bit 1
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 722.4
p2222[0...2] BI: Fixed PID setp. select Bit 2 / BI:PID setp->Bit 2
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 722.5
p2223[0...2] BI: Fixed PID setp. select Bit 3 / BI:PID setp->Bit 3
CU240E
CU240S DP-F
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 0
p2223[0...2] BI: Fixed PID setp. select Bit 3 / BI:PID setp->Bit 3
CU240S
CU240S DP
CU240S PN
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 722.6
r2224 CO: Act. fixed PID setpoint / Fixed.PID setp
Access level: 2 P-Group: Technology Data type: Floating Point
Unit: [%] Data set: -
r2225.0 BO: PID Fixed frequency status / PID FF Status
Access level: 3 P-Group: Commands Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Status of FF Yes No -

Table of Contents