List of Parameters
Parameters
1-29
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Displays valid maximum output current of inverter.
Parameter r0067 is influenced/determined by the following factors:
Rated motor current P0305
Motor overload factor P0640
Motor protection in dependency of P0610
r0067 is less than or equal to maximum inverter current r0209
Inverter protection in dependency of P0290
Note: A reduction of r0067 may indicate an inverter overload or a motor overload.
Description: Displays valid maximum output current of inverter.
Parameter r0067 is influenced/determined by the following factors:
Rated motor current P0305
Motor overload factor P0640
Motor protection in dependency of P0610
r0067 is less than or equal to maximum inverter current r0209
Inverter protection in dependency of P0290
r0067 is affected by the regeneration power limit when regenerating
Note: A reduction of r0067 may indicate an inverter overload or a motor overload.
Description: Displays unfiltered [rms] value of motor current [A]. This value is available filtered (r0027) and unfiltered (r0068).
Note: Used for process control purposes (in contrast to r0027, which is filtered and used as display value).
Description: Displays measured phase currents.
Index: [0] = U_phase
[1] = V_phase
[2] = W_phase
[3] = Offset U_phase
[4] = Offset V_phase
[5] = Offset W_phase
Description: Displays DC-link voltage. This value is available filtered (r0026) and unfiltered (r0070).
Note: Used for process control purposes (in contrast to r0026 (actual DC-link voltage), which is filtered and used as dis-
play value).
r0067 CO: Act. output current limit / Outp cur limit
PM240 Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [A] Data set: -
r0067 CO: Act. output current limit / Outp cur limit
PM250
PM260
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [A] Data set: -
r0068 CO: Output current / Output current
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [A] Data set: -
r0069[0...5] CO: Act. phase currents / Act. phase cur
Access level: 4 P-Group: Closed-loop control Data type: Floating Point
Unit: [A] Data set: -
r0070 CO: Act. DC-link voltage / Act. Vdc
Access level: 3 P-Group: Converter Data type: Floating Point
Unit: [V] Data set: -