F00051 Parameter EEPROM Fault
Reaction: OFF 2
Acknowledge: Quit fault eg. via DI2
Cause: Read or write failure while access to EEPROM.
This can also be caused by the EEPROM being full, too many parameters have been changed.
Remedy: Must be Power Cycled to cancel this bug as some parameters may not be read correct.
Factory Reset and new parameterization, if power cycle does not remove fault
Change inverter control unit
Change some parameters back to default values if the EEPROM is full, then power cycle
Note: r0949 = 1: EEPROM Full
r0949 = 1000 + Block No: Reading data block failed
r0949 = 2000 + Block No: Reading data block timeout
r0949 = 3000 + Block No: Reading data block CRC failed
r0949 = 4000 + Block No: Wrinting data block failed
r0949 = 5000 + Block No: Writing data block timeout
r0949 = 6000 + Block No: writing data block verify failed
r0949 = 7000 + Block No: Reading data block at wrong time
r0949 = 8000 + Block No: writing data block at wrong time
r0949 = 9000 + Block No: Factory Reset did not work becuase restart or power failure