Parameters
List of Parameters
1-178
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Sets continuous torque boost in lower speed range of SLVC (sensorless vector control).
Value is entered in [%] relative to rated motor torque r0333.
Note: P1610 = 100 % corresponds to rated motor torque.
Description: Sets acceleration torque boost in lower speed range of SLVC (sensorless vector control).
Value is entered in [%] relative to rated motor torque r0333.
Note: P1611 = 100 % corresponds to rated motor torque.
Description: Sets time constant of PT1 filter to filter setpoint of torque generating current component in field weakening range.
Description: Enters gain of current controller.
p1610[0...2] Continuous torque boost (SLVC) / Cont. torque boost
Access level: 2 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.0 [%] 200.0 [%] 50.0 [%]
f
t
p1755
i
sd
f(t)
i
sd
(t)
i
sd
(p1610, p1611)
p1610 = p1611 = 0
r0331
p0346
p1611[0...2] Acc. torque boost (SLVC) / Acc trq boost SLVC
Access level: 2 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.0 [%] 200.0 [%] 0.0 [%]
p1654[0...2] Smooth time for Isq setpoint / Isq setp. Tsmooth
Access level: 4 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
2.0 [ms] 20.0 [ms] 6.0 [ms]
p1715[0...2] Gain current controller / Gain current ctrl.
Access level: 4 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.00 5.00 0.25