EasyManua.ls Logo

Siemens Sinamics G120 Series - p1525[0...2] Scaling lower torque limit; Scal. low trq. lim; r1526 CO: Upper torque limitation; Upper trq. lim; r1527 CO: Lower torque limitation; Lower trq. lim

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-174
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Specifies scaling of lower torque limitation in [%].
Note: P1525 = 100 % = standard setting
Description: Displays actual upper torque limitation.
Dependency: The parameters r1526 and r1527 depend on P1520, P1521, P1522, P1523 and P1525.
Description: Displays actual lower torque limitation.
Note: See parameter r1526.
p1525[0...2] Scaling lower torque limit / Scal. low trq. lim
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
-400.0 [%] 400.0 [%] 100.0 [%]
r1526 CO: Upper torque limitation / Upper trq. lim
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [Nm] Data set: -
f
1
~
Torque limitation
Resultant
torque limit
Power
limitation
|f
act
r1526
r1527
Stall
limitation
p1530
p1531
f
1
~
2
Constant
torque
f
stall
Constant
power
|
|M|
Stall
power
r1527 CO: Lower torque limitation / Lower trq. lim
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [Nm] Data set: -

Table of Contents

Related product manuals