Siemens Sinamics G120 Series - r1445 CO: Act. filtered frequency; Act. filt freq; p1452[0...2] Filter time for act.speed (SLVC); Act.spd.filt. SLVC; p1460[0...2] Gain speed controller; Gain of n-ctrl.; p1462[0...2] Integral time speed controller; Tn of n-ctrl.

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-166
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Displays filtered actual speed at speed controller input.
Description: Sets time constant of PT1 filter to filter the speed deviation of speed controller in operation mode SLVC (sensorless
vector control).
Description: Enters gain of speed controller.
Description: Enters integral time of speed controller.
Description: Enters gain of speed controller for sensorless vector control (SLVC).
Description: Enters integral time of speed controller for sensorless vector control (SLVC).
r1445 CO: Act. filtered frequency / Act. filt freq
Access level: 4 P-Group: Closed-loop control Data type: Floating Point
Unit: [Hz] Data set: -
p1452[0...2] Filter time for act.speed (SLVC) / Act.spd.filt. SLVC
Access level: 2 P-Group: Closed-loop control Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
2 [ms] 32000 [ms] 2 [ms]
p1460[0...2] Gain speed controller / Gain of n-ctrl.
CU240S
CU240S DP
CU240S DP-F
CU240S PN
Access level: 2 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.0 2000.0 3.0
p1462[0...2] Integral time speed controller / Tn of n-ctrl.
CU240S
CU240S DP
CU240S DP-F
CU240S PN
Access level: 2 P-Group: Closed-loop control Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
25 [ms] 32001 [ms] 400 [ms]
p1470[0...2] Gain speed controller (SLVC) / Gain n-ctrl (SLVC)
Access level: 2 P-Group: Closed-loop control Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.0 2000.0 3.0
p1472[0...2] Integral time n-ctrl. (SLVC) / Tn of n-ctrl. SLVC
Access level: 2 P-Group: Closed-loop control Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
25 [ms] 32001 [ms] 400 [ms]