Setpoint Channel
Function diagrams
2-359
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Fig. 2-35 5200 – Additional Frequency Modifications (AFM)
SUM or
PID controller
JOG
- 5200 -
Function diagram
87654321
5200_AFM.vsd
Setpoint channel
SINAMICS G120
02.04.2007 V3.0
Additional Frequency Modifications (AFM)
-1
0
1
0
1
r1114
Setp<-dir.ctrl.
x
y
f
IN
f
OUT
RFG
SUM/JOG
selection
(0)
Inh. neg. setp
P1110.CDS
(722.1)
Reverse
P1113.CDS
No evaluation with PID
r1079
Sel. freq.setp [Hz]
Skip frequency
0.00 ... 650.00 [Hz]
P1091.DDS ( 0.00)
Skip frequency 3
0.00 ... 650.00 [Hz]
P1093.DDS ( 0.00)
Skip frequency 2
0.00 ... 650.00 [Hz]
P1092.DDS ( 0.00)
Skip frequency 4
0.00 ... 650.00 [Hz]
P1094.DDS ( 0.00)
Bandwidth
Skip frequency
Skipfreq bandwidth
0.00 ... 10.00 [Hz]
P1101.DDS ( 2.00)
Min. frequency
0.00 ... 650.00 [Hz]
P1080.DDS (0.00)
Resultant max freq [Hz]
r1084
Max. frequency
0.00 ... 650.00 [Hz]
P1082.DDS (50.00)
r1119
Setp before RFG [Hz]