EasyManua.ls Logo

Siemens Sinamics G120 Series - F00055 BOP-EEPROM Fault; F00056 BOP not fitted; F00057 BOP fault; F00058 BOP contents incompatible

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Faults and Alarms
List of Fault and Alarm messages
3-386
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
F00055 BOP-EEPROM Fault
Reaction: OFF 2 (OFF 3)
Acknowledge: Quit fault eg. via DI2
Cause: Read or write failure while saving non-volatile parameter to EEPROM on BOP whilst parameter cloning.
Remedy: Factory Reset and new parameterization
Change BOP
r0949 = 5096 : Use a BOP with a bigger EEPROM
r0949 = 9160 : Use a BOP with a smaller EEPROM
Note: r0949 = 1000 + Block No: Reading data block failed
r0949 = 3000 + Block No: Reading data block CRC failed
r0949 = 4000 + Block No: Writing data block failed
r0949 = 5096 : BOP EEPROM too Small
r0949 = 6000 + Block No: writing data block verify failed
r0949 = 7000 + Block No: Reading data block at wrong time
r0949 = 8000 + Block No: writing data block at wrong time
r0949 = 9160 : Drive EEPROM too Small
F00056 BOP not fitted
Reaction: OFF 2 (OFF 3)
Acknowledge: Quit fault eg. via DI2
Cause: Trying to initiate parameter cloning without BOP fitted.
Remedy: Fit BOP and try again.
F00057 BOP fault
Reaction: OFF 2 (OFF 3)
Acknowledge: Quit fault eg. via DI2
Cause: Parameter cloning with empty BOP.
Parameter cloning with invalid BOP.
Remedy: Download to BOP or replace BOP.
F00058 BOP contents incompatible
Reaction: OFF 2 (OFF 3)
Acknowledge: Quit fault eg. via DI2
Cause: Trying to initiate parameter cloning with BOP created on another type of drive.
Remedy: Download to BOP from this type of drive.
F00060 Asic Timeout
Reaction: OFF 2
Acknowledge: Quit fault eg. via DI2
Cause: Internal communications failure
r0949 = 0: HW reported Link Fail
r0949 = 1: SW reported Link Fail
Remedy: Check connection between inverter power module and inverter control unit
Fault appears sporadically:
Communication failure due to EMC problems
Check - and if necessary - improve EMC
Use EMC filter
Fault appears immediately when mains voltage is applied and an ON command is given.
If fault persists, change inverter.
Contact Service Department.

Table of Contents

Related product manuals