Faults and Alarms
List of Fault and Alarm messages
3-382
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
F00027 Overcurrent on W phase
Reaction: OFF 2
Acknowledge: Quit fault eg. via DI2
Cause: This hardware fault caused by the following events:
Over current trip on W phase
Earth Fault
Remedy: Check Inverter and Motor wiring
F00028 Power limit exceeded during regeneration
Reaction: OFF 2
Acknowledge: Quit fault eg. via DI2
Cause: Occurs if motor is driven by an active load, causing motor to go into excessive regeneration.
Occurs at very high load inertias, when ramping down.
Remedy: Reduce regeneration from active load
Reduce ramp down rate
Increase Imax regeneration limit in p1253
F00029 EM brake overcurrent
Reaction: OFF 2
Acknowledge: Quit fault eg. via DI2
Cause:
Remedy:
F00035 Auto restart after n
Reaction: OFF 2 (OFF 3)
Acknowledge: Power on
Cause: Auto restart attempts exceed value of p1211.
Remedy: