EasyManua.ls Logo

Siemens Sinamics G120 Series - p1500[0...2] Selection of torque setpoint; Torque setp. sel.

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-170
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Selects torque setpoint source.
The selection of settings is detailed in the following table of values, in which the main setpoint is given by the least
significant digit (right-hand position) and the additional setpoint is given by the most significant digit (left-hand posi-
tion). Single digits denote main setpoints that have no additional setpoint.
Values: 0: No main setpoint
2: Analog setpoint
4: USS on RS232
5: USS on RS485
7: Analog setpoint 2
20: No main setpoint + Analog setpoint
22: Analog setpoint + Analog setpoint
24: USS on RS232 + Analog setpoint
25: USS on RS485 + Analog setpoint
27: Analog setpoint 2 + Analog setpoint
40: No main setpoint + USS on RS232
42: Analog setpoint + USS on RS232
44: USS on RS232 + USS on RS232
45: USS on RS485 + USS on RS232
47: Analog setpoint 2 + USS on RS232
50: No main setpoint + USS on RS485
52: Analog setpoint + USS on RS485
54: USS on RS232 + USS on RS485
55: USS on RS485 + USS on RS485
57: Analog setpoint 2 + USS on RS485
70: No main setpoint + Analog setpoint 2
72: Analog setpoint + Analog setpoint 2
74: USS on RS232 + Analog setpoint 2
75: USS on RS485 + Analog setpoint 2
77: Analog setpoint 2 + Analog setpoint 2
Caution: Changing this parameter sets (to default) all settings on item selected. These are the following parameters:
P1503, P1511
p1500[0...2] Selection of torque setpoint / Torque setp. sel.
CU240E
CU240S
Access level: 2 P-Group: Closed-loop control Data type: Unsigned16
Quick comm. YES Active: NO Data set: CDS
Can be changed: C, T
Min Max Factory setting
0 77 0