Description: Defines a limited set of parameters to which the end user will have access.
Instructions for use:
1. Set P0003 = 3 (expert user).
2. Go to P0013 indices 0 to 16 (user list)
3. Enter into P0013 index 0 to 16 the parameters required to be visible in the user-defined list.
The following values are fixed and cannot be changed:
- P0013 index 17 = 3 (user access level)
- P0013 index 18 = 10 (commissioning parameter filter)
- P0013 index 19 = 12 (key for user defined parameter)
4. Set P0003 = 0 to activate the user defined parameter.
Index: [0] = 1st user parameter
[1] = 2nd user parameter
[2] = 3rd user parameter
[3] = 4th user parameter
[4] = 5th user parameter
[5] = 6th user parameter
[6] = 7th user parameter
[7] = 8th user parameter
[8] = 9th user parameter
[9] = 10th user parameter
[10] = 11th user parameter
[11] = 12th user parameter
[12] = 13th user parameter
[13] = 14th user parameter
[14] = 15th user parameter
[15] = 16th user parameter
[16] = 17th user parameter
[17] = 18th user parameter
[18] = 19th user parameter
[19] = 20th user parameter
Dependency: First, set P0011 ("lock") to a different value then P0012 ("key") to prevent changes to user-defined parameter.
Then, set P0003 to 0 to activate the user-defined list.
When locked and the user-defined parameter is activated, the only way to exit the user-defined parameter (and
view other parameters) is to set P0012 ("key") to the value in P0011 ("lock").
Note: The default values of P0011 ("lock") and P0012 ("key") are the same.
p0013[0...19] User defined parameter / User-defined par
Access level: 3 P-Group: - Data type: Unsigned16
Quick comm. NO Active: NO Data set: -
Can be changed: C, U, T
Min Max Factory setting
0 65535 0