Parameters
List of Parameters
1-32
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Selects source of display for PZD signals.
Index: [0] = 1st PZD signal
[1] = 2nd PZD signal
[2] = 3rd PZD signal
[3] = 4th PZD signal
[4] = 5th PZD signal
[5] = 6th PZD signal
[6] = 7th PZD signal
[7] = 8th PZD signal
[8] = 9th PZD signal
[9] = 10th PZD signal
Description: Displays PZD signals in [%].
Index: [0] = 1st PZD signal
[1] = 2nd PZD signal
[2] = 3rd PZD signal
[3] = 4th PZD signal
[4] = 5th PZD signal
[5] = 6th PZD signal
[6] = 7th PZD signal
[7] = 8th PZD signal
[8] = 9th PZD signal
[9] = 10th PZD signal
Note: r0096 = 100 % corresponds to 4000 hex.
Description: Determines whether power settings are expressed in [kW] or [hp] (e.g. Rated motor power P0307).
The default settings for the rated motor frequency P0310 and maximum frequency P1082 are also set automatically
here, in addition to reference frequency P2000.
Values: 0: Europe [kW], motor base frequency is 50 Hz
1: North America [hp], motor base frequency is 60 Hz
2: North America [kW], motor base frequency is 60 Hz
Dependency: Where:
Stop drive first (i.e. disable all pulses) before you change this parameter.
Parameter P0100 can only be changed with P0010 = 1 (Commissioning mode) via the respective interface (e.g.
USS on RS232).
Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated motor
parameters (see P0340 - calculation of motor parameters).
p0095[0...9] CI: Display PZD signals / PZD signals
Access level: 3 P-Group: Closed-loop control Data type: Unsigned32
Quick comm. NO Active: NO Data set: -
Can be changed: T
Min Max Factory setting
- - 0
r0096[0...9] PZD signals / PZD signals
Access level: 3 P-Group: Closed-loop control Data type: Floating Point
Unit: [%] Data set: -
p0100 Europe / North America / Europe / Nth Amer.
Access level: 1 P-Group: - Data type: Unsigned16
Quick comm. YES Active: NO Data set: -
Can be changed: C
Min Max Factory setting
0 2 0