Parameters
List of Parameters
1-228
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Defines threshold current in [%] relative to P0305 (rated motor current) to be used in comparisons of I_act and
I_Thresh as illustrated in the diagram below.
Note: This threshold controls bit 3 in status word 3 (r0053).
Description: Defines delay time prior to activation of current comparison.
Note: See diagram in P2170 (threshold current I_thresh)
p2170[0...2] Threshold current I_thresh / Threshold current
Access level: 3 P-Group: Messages Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.0 [%] 400.0 [%] 100.0 [%]
0
1
Threshold current
0.0 ... 400.0 [%]
P2170.D (100.0)
Delay time current
0 ... 10000 [ms]
P2171.D (10)
I_act
| I_act | > I_thresh
|I_act| > I_thresh
0T
r0053 Bit03
p2171[0...2] Delay time current / Delay time current
Access level: 3 P-Group: Messages Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0 [ms] 10000 [ms] 10 [ms]