Parameters
List of Parameters
1-114
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Selects frequency setpoint source.
The selection of settings is detailed in the following table of values, in which the main setpoint is given by the least 
significant digit (right-hand position) and the additional setpoint is given by the most significant digit (left-hand posi-
tion). Single digits denote main setpoints that have no additional setpoint.
Values: 0: No main setpoint
1: MOP setpoint
2: Analog setpoint
3: Fixed frequency
4: USS on RS232
6: Fieldbus
7: Analog setpoint 2
10: No main setpoint  +  MOP setpoint
11: MOP setpoint       +  MOP setpoint
12: Analog setpoint    +  MOP setpoint
13: Fixed frequency    +  MOP setpoint
14: USS on RS232     +  MOP setpoint
16: Fieldbus                +  MOP setpoint
17: Analog setpoint 2  +  MOP setpoint
20: No main setpoint   +  Analog setpoint
21: MOP setpoint        +  Analog setpoint
22: Analog setpoint     +  Analog setpoint
23: Fixed frequency    +  Analog setpoint
24: USS on RS232     +  Analog setpoint
26: Fieldbus                +  Analog setpoint
27: Analog setpoint 2  +  Analog setpoint
30: No main setpoint   +  Fixed frequency
31: MOP setpoint        +  Fixed frequency
32: Analog setpoint     +  Fixed frequency
33: Fixed frequency    +  Fixed frequency
34: USS on RS232     +  Fixed frequency
36: Fieldbus                +  Fixed frequency
37: Analog setpoint 2  +  Fixed frequency
40: No main setpoint   +  USS on RS232
41: MOP setpoint        +  USS on RS232
42: Analog setpoint     +  USS on RS232
43: Fixed frequency    +  USS on RS232
44: USS on RS232     +  USS on RS232
46: Fieldbus                +  USS on RS232
47: Analog setpoint 2  +  USS on RS232
60: No main setpoint    +  Fieldbus
61: MOP setpoint         +  Fieldbus
62: Analog setpoint     +  Fieldbus
63: Fixed frequency     +  Fieldbus
64: USS on RS232      +  Fieldbus
66: Fieldbus                 +  Fieldbus
67: Analog setpoint 2   +  Fieldbus
70: No main setpoint    +  Analog setpoint 2
71: MOP setpoint          +  Analog setpoint 2
72: Analog setpoint       +  Analog setpoint 2
73: Fixed frequency       +  Analog setpoint 2
74: USS on RS232        +  Analog setpoint 2
76: Fieldbus                  +  Analog setpoint 2
77: Analog setpoint 2    +  Analog setpoint 2
Caution: Changing this parameter sets (to default) all settings on item selected. These are the following parameters:
P1070, P1071, P1075, P1076
p1000[0...2] Selection of frequency setpoint / Freq setp. select.
CU240S DP
CU240S DP-F
CU240S PN
Access level: 1 P-Group: Setpoints Data type: Unsigned16
Quick comm. YES Active: NO Data set: CDS
Can be changed: C, T
Min Max Factory setting 
0 77 6