Description: Defines Fixed PID Setpoint 13
Note: See P2201 (Fixed PID Setpoint 1).
Description: Defines Fixed PID Setpoint 14
Note: See P2201 (Fixed PID Setpoint 1).
Description: Defines Fixed PID Setpoint 15
Note: See P2201 (Fixed PID Setpoint 1).
Description: Fixed frequencies for PID setpoint can be selected in two different modes. Parameter P2216 defines the mode.
Values: 1: Direct selection
2: Binary selection
Description: Defines command source of fixed PID setpoint selection Bit 0.
p2213[0...2] Fixed PID setpoint 13 / Fixed PID setp. 13
Access level: 2 P-Group: Technology Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
-200.00 [%] 200.00 [%] 120.00 [%]
p2214[0...2] Fixed PID setpoint 14 / Fixed PID setp. 14
Access level: 2 P-Group: Technology Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
-200.00 [%] 200.00 [%] 130.00 [%]
p2215[0...2] Fixed PID setpoint 15 / Fixed PID setp. 15
Access level: 2 P-Group: Technology Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
-200.00 [%] 200.00 [%] 130.00 [%]
p2216[0...2] Fixed PID setpoint mode / Fix.PID Mode
Access level: 2 P-Group: Technology Data type: Unsigned16
Quick comm. NO Active: NO Data set: DDS
Can be changed: T
Min Max Factory setting
1 2 1
p2220[0...2] BI: Fixed PID setp. select Bit 0 / BI:PID setp->Bit 0
Access level: 3 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: T
Min Max Factory setting
- - 722.3