Description: Threshold_2 for comparing speed or frequency to thresholds as illustrated in the diagram below.
Description: When comparing speed or frequency to threshold f_2 (P2157).
This is the time delay before status bits are cleared.
Note: See diagram in P2157 (threshold frequency f_2)
p2157[0...2] Threshold frequency f_2 / Threshold freq f_2
Access level: 2 P-Group: Messages Data type: Floating Point
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0.00 [Hz] 650.00 [Hz] 30.00 [Hz]
Tconst. speed filt
0 ... 1000 [ms]
P2153.D (5)
Threshold freq f_2
0.00 ... 650.00 [Hz]
P2157.D (30.00)
Hyst. freq. f_hys
0.00 ... 10.00 [Hz]
P2150.D (3.00)
Delay time of f_2
0 ... 10000 [ms]
P2158.D (10)
Delay time of f_2
0 ... 10000 [ms]
P2158.D (10)
| f_act | <= f_2
| f_act | > f_2
T0
T0
f_act
r2198 Bit01
r2198 Bit00
| f_act | <= f_2
Threshold freq f_2
0.00 ... 650.00 [Hz]
P2157.D (30.00)
Hyst. freq. f_hys
0.00 ... 10.00 [Hz]
P2150.D (3.00)
0
1
{
0
1
{
| f_act | > f_2
r2169
p2158[0...2] Delay time of threshold freq f_2 / Delay time of f_2
Access level: 2 P-Group: Messages Data type: Unsigned16
Quick comm. NO Active: YES Data set: DDS
Can be changed: U, T
Min Max Factory setting
0 [ms] 10000 [ms] 10 [ms]