Siemens Sinamics G120 Series - r1204 Status word: Flying start V;f; Stat: Flystart V;f; r1205 Status word: Flying start SLVC; Stat Flystart SLVC

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-140
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Bit parameter for checking and monitoring states during search, if V/f control mode is selected (P1300 < 20).
Description: Bit parameter for checking status of flying start performed with n-adaption of observer.
Parameter is only valid, if sensorless vector control (SLVC)) is selected (P1300 = 20, 22).
r1204 Status word: Flying start V/f / Stat: Flystart V/f
Access level: 4 P-Group: - Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Current applied Yes No -
01 Current could not be applied Yes No -
02 Voltage reduced Yes No -
03 Slope-filter started Yes No -
04 Current less threshold Yes No -
05 Current-minimum Yes No -
07 Speed could not be found Yes No -
r1205 Status word: Flying start SLVC / Stat Flystart SLVC
Access level: 3 P-Group: - Data type: Unsigned16
Unit: - Data set: -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Transformation active Yes No -
01 Initialize n-adaption Yes No -
02 Current applying Yes No -
03 n-controller closed Yes No -
04 Isd-controller open Yes No -
05 RFG hold Yes No -
06 n-adaption set to zero Yes No -
07 reserved Yes No -
08 reserved Yes No -
09 reserved Yes No -
10 Direction Positive Yes No -
11 Search is started Yes No -
12 Current is applied Yes No -
13 Search is aborted Yes No -
14 Deviation is zero Yes No -
15 n-controller is active Yes No -