Function diagrams
Internal Setpoint Source
2-340
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Fig. 2-19 3310 – Fixed PID setpoint, Binary Selection (P2216 = 2)
- 3310 -
Function diagram
87654321
3310_FPID.vsd
Internal Setpoint Source
SINAMICS G120
02.04.2007 V3.0
Fixed PID setpoint, Binary Selection (P2216 = 2)
0 0 0 1
0 1 0 1
0 1 1 0
1 1 1 1
.
.
.
.
.
.
.
.
.
.
.
.
0 1 0 0
(722.3)
BI:PID setp->Bit 0
P2220.CDS
(722.4)
BI:PID setp->Bit 1
P2221.CDS
(722.5)
BI:PID setp->Bit 2
P2222.CDS
(722.6)
BI:PID setp->Bit 3
P2223.CDS
PID FF Status
r2225
r2224
Fixed.PID setp [%]
Fixed PID setp. 1
-200.00 ... 200.00 [%]
P2201.DDS ( 0.00)
Fixed PID setp. 4
-200.00 ... 200.00 [%]
P2204.DDS ( 30.00)
Fixed PID setp. 5
-200.00 ... 200.00 [%]
P2205.DDS ( 40.00)
Fixed PID setp. 6
-200.00 ... 200.00 [%]
P2206.DDS ( 50.00)
Fixed PID setp. 15
-200.00 ... 200.00 [%]
P2215.DDS ( 130.00)