EasyManua.ls Logo

Siemens Sinamics G120 Series - p0731[0...2] BI: Function of digital output 0; Fct. of DO0; p0732[0...2] BI: Function of digital output 1; Fct. of DO1; p0733[0...2] BI: Function of digital output 2; Fct. of DO2

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Parameters
Parameters
1-83
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Defines source of digital output 0.
Notice: An inverse logic can be realised by inverting the digital outputs in P0748.
Note: Output of fault bit 52.3 is inverted on digital output.
Monitor functions ==> see parameter r0052, r0053
Motor holding brake ==> see parameter P1215
DC-Brake ==> see parameter P1232, P1233
Description: Defines source of digital output 0.
Notice: An inverse logic can be realised by inverting the digital outputs in P0748.
Note: Output of fault bit 52.3 is inverted on digital output.
Monitor functions ==> see parameter r0052, r0053
Motor holding brake ==> see parameter P1215
Description: Defines source of digital output 1.
Description: Defines source of digital output 2.
p0731[0...2] BI: Function of digital output 0 / Fct. of DO0
PM240 Access level: 2 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: U, T
Min Max Factory setting
- - 52.3
p0731[0...2] BI: Function of digital output 0 / Fct. of DO0
PM250
PM260
Access level: 2 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: U, T
Min Max Factory setting
- - 52.3
p0732[0...2] BI: Function of digital output 1 / Fct. of DO1
Access level: 2 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: U, T
Min Max Factory setting
- - 52.7
p0733[0...2] BI: Function of digital output 2 / Fct. of DO2
Access level: 2 P-Group: Commands Data type: Unsigned32
Quick comm. NO Active: NO Data set: CDS
Can be changed: U, T
Min Max Factory setting
- - 0