Siemens Sinamics G120 Series - p0725 PNP; NPN digital inputs; PNP;NPN DI; p0727[0...2] Selection of 2;3-wire method; 2;3-wire selection; r0730 Number of digital outputs; Number of DO

Siemens Sinamics G120 Series
418 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of Parameters
1-82
© Siemens AG 2007 All Rights Reserved
SINAMICS G120 Control Units CU240S, Edition 05/2007
Description: Switches between active high (PNP) and active low (NPN).
This is valid for all digital inputs simultaneously.
The following is valid by using the internal supply:
Values: 0: NPN mode ==> low active
1: PNP mode ==> high active
Description: Determines the control method using the terminals. This parameter allows the selection of the control philosophy.
The control philosophies exclude each other.
Values: 0: Siemens (start/dir)
1: 2-wire (fwd/rev)
2: 3-wire (fwd/rev)
3: 3-wire (start/dir)
Note: Where:
P denotes Pulse
FWD denotes FORWARD
REV denotes REVERSE
When any of the control functions are selected using P0727, the setting for the digital inputs (P0701 - P0704) are
redefined as follows:
Regarding the use of fixed frequencies see P1000 and P1001.
Description: Displays number of digital outputs (relays).
p0725 PNP / NPN digital inputs / PNP/NPN DI
CU240E Access level: 3 P-Group: Commands Data type: Unsigned16
Quick comm. NO Active: YES Data set: -
Can be changed: T
Min Max Factory setting
0 1 1
p0727[0...2] Selection of 2/3-wire method / 2/3-wire selection
Access level: 2 P-Group: - Data type: Unsigned16
Quick comm. YES Active: NO Data set: CDS
Can be changed: C, T
Min Max Factory setting
0 3 0
Settings
P0701 - P0704
P0727 = 0
(Siemens Standard
Control)
P0727 = 1
(2-wire Control)
1 STOP
2
12
Redefined Digital Inputs
P0727 = 2
(3-wire Control)
P0727 = 3
(3-wire Control)
ON/OFF1
ON_REV/OFF1
ON_FWD ON_PULSE
ON_REV OFF1/HOLD
REV REV REVP REV
FWDP
r0730 Number of digital outputs / Number of DO
Access level: 3 P-Group: Commands Data type: Unsigned16
Unit: - Data set: -