4-25
Group 02: IM Motor Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
02-00
No-Load Current
of Motor1
0.01~600.00 - A O X X X X X O
02-01
Rated Current of
Motor1
Modes of V/F, V/F+PG
are
10%~200% of
inverter’s rated current.
Modes of SLV, SV are
25%~200% of inverter’s
rated current.
- A O O O O X X O
02-02 Reserved
02-03
Rated Rotation
Speed of Motor1
0~60000 - Rpm O O O O X X O
02-04
Rated Voltage of
Motor1
200V: 50.0~240.0 220.0
V O O O O X X O
400V: 100.0~480.0 440.0
575V: 150.0~670.0 575.0
690V: 200.0~804.0 690.0
02-05
Rated Power of
Motor1
0.01~600.00 - kW O O O O X X O
02-06
Rated Frequency
of Motor1
5.0~599.0 60.0 Hz O O O O X X O
02-07 Poles of Motor 1 2~16(Even) 4 - O O O O X X O
02-08 Reserved
02-09
Excitation Current
of Motor 1
15%~70% of Motor
Rated Current
- % X X O O X X X
02-10
Core Saturation
Coefficient 1
of Motor 1
1~100 - % X X O O X X X
02-11
Core Saturation
Coefficient 2
of Motor 1
1~100 - % X X O O X X X
02-12
Core Saturation
Coefficient 3
of Motor 1
80~300 - % X X O O X X X
02-13
Core loss of
Motor 1
0.0~15.0 - % O O X X X X O
02-14 Reserved
02-15
Resistance
between Wires of
Motor 1
0.001~60.000 - Ω O O O O X X O
02-16
Reserved
02-17
02-18
02-19
No-Load Voltage
of Motor 1
200V: 50~240 -
V X X O O X X X 400V: 100~480 -
575V: 420~600 -