Programming errors:
1. Check that all Psets are configured from the Sync reference.
2. Check that all Sync members have T200 Tool start select source set to Sync start.
3. Check that all Sync members have C317 Sync reference IP set to the IP-address of the
Sync reference.
4. Reboot any reprogrammed Sync member or Sync reference.
Hardware-related errors:
1. Check that the I/O Bus cables between the Sync members is correctly connected and
without faults.
2. Check that the remote start connector in the Sync members is correctly wired for
remote start.
Error elimination:
1. Select a new Pset from the Sync reference. If all Sync members change to the same
Pset, the Sync group programming is correct. If not, check the programming and the
Ethernet cables and connections.
2. Select normal loosening and start a loosening from the Sync reference. If not all Sync
members start, check the tool trigger configuration in the Sync members and the
wiring of the remote start input. Check also the I/O Bus connection and the I/O Bus
cabling.
3. If a single spindle does not start, the tool, tool-cable or controller might be broken. If
all spindles in the group start loosening but not tightening, check that all Psets are
configured in the same way. If not, restore them again from the Sync reference (all
Psets must be configured from the Sync reference).