Fieldbus
9836 3123 01 239 (428)
Connector
Connector RJ45 standard Ethernet connector is used.
Address dipswitch
A dipswitch with 8 positions is used to configure the low byte of the IP address.
IP configuration
The IP configuration can be set with DIP switch or mailbox message. Subnet mask is always
255.255.255.0, gateway is not used.
The different IP configuration options (see table below).
Configure via ToolsTalk PF
Software setting overrides the DIP switch.
Use 192.168.250.X where X is set with the DIP switch. See
RFC 1918.
This is the preferred method for FL-NET.
Must be set before power on.
15.8.10 CC-Link
CC-Link is an open-architecture network managed by the CC-Link Partner Association (CLPA). For more
information visit http://www.cc-link.org
In brief:
ï‚· Baud rate can be selected among 156k, 625k, 2.5M, 5M and 10 M.
ï‚· Based on RS485 with networks up to 1.2 km, or extended to 13.2 km with repeaters
ï‚· 64 stations per network
ï‚· Refresh time of <3.9mSecs for 65 I/O stations (distance dependent)
ï‚· Master/Slave network with Floating Masters and hot swap of stations
Hardware
ï‚· Transmission media: shielded 3 line copper wire
ï‚· Topology: trunk line, multi drop
ï‚· FieldBus connectors: M12, CLPA, D-Sub9
ï‚· PF connector: 5 pin DeviceNet/CANopen Open Style Connector