Event codes
9836 3123 01 405 (428)
Trend deviation alarm, the subgroup CM range value has
been below the average range value of the average of the
latest ten subgroups 7 times consecutively.
Trend deviation alarm, the last subgroup CM average is
outside XCM-bar-bar-2 sigma.
Trend deviation alarm, the last subgroup CM range
average is outside RCM-bar-bar-2 sigma.
23.1.5 E400-E499 Communication events
Duplicate device
IDs on I/O bus
Two I/O devices with the same ID are
present on the I/O bus. This event occurs
even if the devices are not configured in
PF.
Acknowledge the event.
Make sure that all of the devices on the
bus have a unique ID.
I/O device not
responding
I/O device is not properly connected or the
ID of the device is not the same as the one
configured.
Additional parameter information:
First integer parameter: Number of device
not responding.
Check IO cables.
Check the configuration of the
accessories on the IO bus and compare
it with the devices on the IO bus.
IO device has
invalid ID
selected
An I/O device has selected ID 0, which is
invalid.
Additional parameter information:
First integer parameter: Number of device
not responding.
On the device, select an ID between 1
and 15 (in ToolsTalk) or 1-F (on
selector)
Too many
communication
sessions at one
time
There are too many connections at the
same time (ToolsTalk PF, Tools Net,
Operator Panel etc.) The most common
problem is that an external program
allocates all the communication.
Wait until the other sessions are done
and close their connection.
ST Accessory not
supported.
A device connected to the ST-bus is not
recognized by PF.
Acknowledge the event.
Upgrade PF software.
Safety trigger not
supported by tool
software
The tool software version does not support
safety trigger function.
Acknowledge the event.
Upgrade the tool software.