Fieldbus
242 (428) 9836 3123 01
Example:
Address = (Left Switch Setting x 10) + (Right Switch Setting x 1)
Left switch is set to 5 and right switch is set to 2. This gives a node address of 52.
If you want to set the node address from TT the switches must be set to 99.
The node address can not be changed when the power is switched on.
The SW1 and SW2 are 2 most right placed!
Baud rate
The baud rate on a CC-Link network is set during configuration of the master and only one baud rate is
possible in a CC-Link installation.
Baud Rate Switch (SW3).This rotary switch is used to specify the baudrate of the module. This can also be
specified by software (TTPF), in this case the switch must be set to ‘9’.
The SW3 is placed to the left of SW1 and SW2!
Bauds rates supported by PF
CC-Link Configuration
Set node address and baud rate from
If set from “Software” backplane switches SW1 to SW3 should be set all to 9 (9-9-9). When “Hardware”
is selected refer to information in APPENDIX B about configuring switches.
Note: PF reboot is needed after change!
Baud Rate
Baud rate can be selected among 156k, 625k, 2.5M, 5M and 10 M.