Event codes
9836 3123 01 397 (428)
The user is trying to allocate more
memory than exists in the Power Focus.
Check settings for Controller >
Memory.
Decrease the number of results, Psets
or Jobs until the memory usage is
below 100%.
Totally
configurable
memory needed
Not possible to configure this functionality
without function “totally configurable
memory”.
Save the PF configuration to file.
Open Controller > Memory.
C600 Memory type must be set to
Totally configurable memory.
Reboot PF, the PF memory is
remapped and erased.
Reload the configuration without the
memory settings.
Attempt to scan from wrong source.
Open PF Map > Accessories > Tool
bus and double click Configuration.
In the Tool bus configuration dialog
box, click ST scanner.
Ensure that the Scanner source item
list selection is applicable.
The ST scanner temperature has exceeded
max temperature.
Disconnect the tool
Let the scanner cool for 15 minutes
Not possible to
store Reference
Trace
If You try to store the Reference
Trace(In Multiple Traces menu), but it
does not exist anymore.
Make new tightenings and find a
new Reference Trace and press
store again.