Section 7. Installation
'Main Program
BeginProg
Scan(1,Sec,1,0)
'Reset and Increment Counter
If Oscillator = 2 Then Oscillator = 0
Oscillator = Oscillator + 1
'Process and Control
If Oscillator = 1
If Flag(1) = True Then
DisableVar = True
EndIf
Else
DisableVar = False
EndIf
'Call Data Tables and Store Data
CallTable(OscAvgData)
NextScan
EndProg
Numbers of Records
The exact number of records that can be stored in a data table is governed by a
complex set of rules, the summary of which can be found in the appendix
Numbers of Records in Data Tables
(p. 466).
7.8.4.10.2 Declaring Subroutines
Read More See section Subroutines (p. 288) for more information on programming
with subroutines.
Subroutines allow a section of code to be called by multiple processes in the main
body of a program. Subroutines are defined before the main program body of a
program.
Note A particular subroutine can be called by multiple program sequences
simultaneously. To preserve measurement and processing integrity, the CR1000
queues calls on the subroutine, allowing only one call to be processed at a time in
the order calls are received. This may cause unexpected pauses in the conflicting
program sequences.
7.8.4.10.3 'Include' File
An alternative to a subroutine is an 'include' file. An 'include' file is a CRBasic
program file that resides on the CR1000 CPU: drive and compiles as an insert to
the CRBasic program. It may also run on its own
(p. 116). It is essentially a
subroutine stored in a file separate from the main program file. It can be used
once or multiple times by the main program, and by multiple programs. The file
begins with the SlowSequence instruction and can contain any code.
Procedure to use the "Include File":
1. Write the file, beginning with the SlowSequence instruction followed by any
other code.
147

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Campbell CR1000 and is the answer not in the manual?

Campbell CR1000 Specifications

General IconGeneral
Power Requirements9.6 to 16 VDC
Data Logger Operating SystemCRBasic
Memory4 MB
Analog Inputs16 single-ended or 8 differential
Analog Input Resolution13 bits
Analog Input Range+/-2.5V
Digital I/O8
Pulse Counters2
Communication PortsRS-232
Operating Temperature-25°C to +50°C
Pulse Channels4