Appendix A. CRBasic Programming Instructions
WebPageBegin / WebPageEnd
Declares a web page that is displayed when a request for the defined HTML page
comes from an external source.
Syntax
WebPageBegin("WebPageName", WebPageCmd)
HTTPOut("<p>html string to output " + variable + " additional
string to output</p>")
HTTPOut("<p>html string to output " + variable + " additional
string to output</p>")
WebPageEnd
XMLParse()
Reads and parses an XML file in the datalogger.
Syntax
XMLParse(XMLContent, XMLValue, AttrName, AttrNameSpace,
ElemName, ElemNameSpace, MaxDepth, MaxNameSpaces)
A.18 Modem Control
Read More For help on datalogger-initiated telecommunication, see Initiating
Telecomms (Callback) (p. 392).
DialModem
Sends a modem-dial string out a datalogger communication port.
Syntax
DialModem(ComPort, BaudRate, DialString, ResponseString)
ModemCallback
Initiates a call to a computer via a phone modem.
Syntax
ModemCallback(Result, COMPort, BaudRate, Security,
DialString, ConnectString, Timeout, RetryInterval,
AbortExp)
ModemHangup / EndModemHangup
Encloses code that should be run when a COM port hangs up communication.
Syntax
ModemHangup(ComPort)
[instructions to be run upon hang-up]
EndModemHangup
A.19 SCADA
Read More See sections DNP3 (p. 408) and Modbus (p. 411).
Modbus and DNP3 instructions run as process tasks.
597

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Campbell CR1000 and is the answer not in the manual?

Campbell CR1000 Specifications

General IconGeneral
Power Requirements9.6 to 16 VDC
Data Logger Operating SystemCRBasic
Memory4 MB
Analog Inputs16 single-ended or 8 differential
Analog Input Resolution13 bits
Analog Input Range+/-2.5V
Digital I/O8
Pulse Counters2
Communication PortsRS-232
Operating Temperature-25°C to +50°C
Pulse Channels4