EasyManuals Logo
Home>Campbell>Measuring Instruments>CR1000

Campbell CR1000 User Manual

Campbell CR1000
678 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #237 background imageLoading...
Page #237 background image
Section 7. Installation
Table 36. PRTCalc() Type-Code-2 Sensor
US Industrial Standard, alpha = 0.00392 (Reference: Logan Enterprises)
Constant Coefficient
a 3.9786300E-03
d -2.3452400E-06
e 1.8174740E-05
f -1.1726200E-06
g 1.7043690E+00
h -2.7795010E+00
i 8.8078440E+00
j 2.5129740E+02
Table 37. PRTCalc() Type-Code-3 Sensor
US Industrial Standard, alpha = 0.00391 (Reference: OMIL R84 (2003))
Constant Coefficient
a 3.9690000E-03
d -2.3364000E-06
e 1.8089360E-05
f -1.1682000E-06
g 1.7010560E+00
h -2.6953500E+00
i 8.8564290E+00
j 2.5190880E+02
Table 38. PRTCalc() Type-Code-4 Sensor
Old Japanese Standard, alpha = 0.003916 (Reference: JIS C 1604:1981, National Instruments)
Constant Coefficient
a 3.9739000E-03
d -2.3480000E-06
e 1.8139880E-05
f -1.1740000E-06
g 1.7297410E+00
h -2.8905090E+00
i 8.8326690E+00
j 2.5159480E+02
237

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Campbell CR1000 and is the answer not in the manual?

Campbell CR1000 Specifications

General IconGeneral
BrandCampbell
ModelCR1000
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals