Section 7. Installation
Table 36. PRTCalc() Type-Code-2 Sensor
US Industrial Standard, alpha = 0.00392 (Reference: Logan Enterprises)
Constant Coefficient
a 3.9786300E-03
d -2.3452400E-06
e 1.8174740E-05
f -1.1726200E-06
g 1.7043690E+00
h -2.7795010E+00
i 8.8078440E+00
j 2.5129740E+02
Table 37. PRTCalc() Type-Code-3 Sensor
US Industrial Standard, alpha = 0.00391 (Reference: OMIL R84 (2003))
Constant Coefficient
a 3.9690000E-03
d -2.3364000E-06
e 1.8089360E-05
f -1.1682000E-06
g 1.7010560E+00
h -2.6953500E+00
i 8.8564290E+00
j 2.5190880E+02
Table 38. PRTCalc() Type-Code-4 Sensor
Old Japanese Standard, alpha = 0.003916 (Reference: JIS C 1604:1981, National Instruments)
Constant Coefficient
a 3.9739000E-03
d -2.3480000E-06
e 1.8139880E-05
f -1.1740000E-06
g 1.7297410E+00
h -2.8905090E+00
i 8.8326690E+00
j 2.5159480E+02
237

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Campbell CR1000 and is the answer not in the manual?

Campbell CR1000 Specifications

General IconGeneral
Power Requirements9.6 to 16 VDC
Data Logger Operating SystemCRBasic
Memory4 MB
Analog Inputs16 single-ended or 8 differential
Analog Input Resolution13 bits
Analog Input Range+/-2.5V
Digital I/O8
Pulse Counters2
Communication PortsRS-232
Operating Temperature-25°C to +50°C
Pulse Channels4