Section 8. Operation
Table 109. API Commands, Parameters, and Arguments
Parameter
Commands in which the
parameter is used Function of parameter Argument(s)
format
BrowseSymbols
DataQuery
ClockSet
ClockCheck
FileControl
ListFiles
Specifies response format.
html, xml, json:
apply to all
commands listed in
column 2.
toa5 and tob1 apply
only to DataQuery
mode DataQuery
Specifies range of data with
which to respond.
most-recent
since-time
since-record
data-range
backfill
p1 DataQuery
maximum number of
records (when using
most-recent
argument).
beginning date and/or
time (when using
since-time ,or date-
range arguments).
beginning record
number (when using
since-record
argument).
interval in seconds
(when using backfill
argument).
integer number of
records (when using
most-recent
argument)
time in defined
format (when using
since-time ,or date-
range arguments,
see Time Syntax (p.
427)
section)
integer record
number(when using
since-record
argument).
integer number of
seconds (when using
backfill argument).
p2 DataQuery
Specifies ending date and/or
time when using date-range
argument.
time expressed in defined
format (see Time Syntax
(p.
427)
section)
value SetValueEx
Specifies the new value. numeric or string
time ClockSet
Specifies set time. time in defined format
action FileControl
Specifies FileControl action. 1 through 20
file FileControl
Specifies first argument of
FileControl action.
file name with drive
file2 FileControl
Specifies second argument
parameter of FileControl
action.
file name with drive
426

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Campbell CR1000 and is the answer not in the manual?

Campbell CR1000 Specifications

General IconGeneral
Power Requirements9.6 to 16 VDC
Data Logger Operating SystemCRBasic
Memory4 MB
Analog Inputs16 single-ended or 8 differential
Analog Input Resolution13 bits
Analog Input Range+/-2.5V
Digital I/O8
Pulse Counters2
Communication PortsRS-232
Operating Temperature-25°C to +50°C
Pulse Channels4