EasyManuals Logo

Campbell CR1000 User Manual

Campbell CR1000
678 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #447 background imageLoading...
Page #447 background image
Section 8. Operation
HTML tabular response:
HTML page source:
<!DOCTYPE HTML PUBLIC "-//W3C//DTD HTML 4.01 Transitional//EN"
"http://www.w3.org/TR/html4/loose.dtd">
<!DOCTYPE HTML PUBLIC "-//IETF//DTD HTML//EN"><html>
<head><title>ListFiles Response</title></head>
<body><h1>ListFiles Response</h1><table border="1">
<tr><td><b>Path</b></td>
<td><b>Is Directory</b></td>
<td><b>Size</b></td>
<td><b>Last Write</b></td>
<td><b>Run Now</b></td>
<td><b>Run On Power Up</b></td>
<td><b>Read Only</b></td>
<td><b>Paused</b></td></tr><tr>
<td>CPU/</td>
<td>true</td>
<td>443904</td>
<td>2012-06-22T00:00:00</td>
<td>false</td>
<td>false</td>
<td>false</td>
<td>false</td></tr><tr>
<td>CPU/ModbusMasterTCPExample.CR1</td>
<td>false</td>
<td>967</td>
<td>2012-07-10T18:21:44</td>
<td>false</td>
<td>false</td>
<td>false</td>
<td>false</td></tr><tr>
<td>CPU/CS475-Test.CR1</td>
<td>false</td>
<td>828</td><td>2012-07-16T14:16:50</td>
<td>false</td>
<td>false</td>
<td>false</td>
<td>false</td></tr><tr>
<td>CPU/DoubleModbusSlaveTCP.CR1</td>
<td>false</td>
<td>1174</td>
<td>2012-07-31T17:18:00</td>
<td>false</td>
<td>false</td>
<td>false</td>
<td>false</td></tr><tr>
447

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Campbell CR1000 and is the answer not in the manual?

Campbell CR1000 Specifications

General IconGeneral
Power Requirements9.6 to 16 VDC
Data Logger Operating SystemCRBasic
Memory4 MB
Analog Inputs16 single-ended or 8 differential
Analog Input Resolution13 bits
Analog Input Range+/-2.5V
Digital I/O8
Pulse Counters2
Communication PortsRS-232
Operating Temperature-25°C to +50°C
Pulse Channels4

Related product manuals