5-122 F650 DIGITAL BAY CONTROLLER GEK-106310-AF
5.5 CONTROL ELEMENTS CHAPTER 5: SETPOINTS
Figure 5-31: Fuse failure element block diagram
5.5.6 Pulse counters
The F650 includes eight pulse counters, each pulse counter stores the activation number to that pulse counter. This value
can be multiplied for a factor selectable by setting.
The inputs used in this pulse counter function can be selected from all the available in the F650 device. Take into account
that the input/output settings are both set for the generic input as well as for the pulse counter input, e.g. Debounce time.
Pulse Counters settings are:
CntPulses Enabled: Enable/disable each pulse counter.
CntPulses Name: Each pulse counter can have a configurable user name.
CntPulses Factor: This is the factor multiplier applied to the input activations number stored in the
pulse counter, providing possibilities to adjust the obtained value to any scale. It the
"CntPulses Factor X" is set to zero it takes no effect.
CntPulses Overflow: It is the maximum value set as result of the CntPulses Factor plus the number of
inputs activation. This means that after reaching that value, the pulse counter value
starts counting from zero.
CntPulses Board Origin: Board selection for the pulse counter input.
SETPOINT > CONTROL ELEMENTS > PULSE COUNTERS
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
Pulse counter enabling setting CntPulses Enabled X DISABLED N/A [DISABLED – ENABLED]
Name of the pulse counter CntPulses Name X Pulse Counter X N/A N/A
Multiplier factor for the pulse counter CntPulses Factor X 1.000 0.001 [0.000 : 65000.000]
Overflow value for the pulse counter CntPulses Overflow X 65535 1 [0 : 1000000]
Board selection for the pulse counter CntPulses Board Origin X F N/A [F,G,H,I]
Input index inside the selected board CntPulses Input Origin X 1 1 [1 : 32]
Note: X is the pulse counter index, up to 8.