APPENDIX D: IEC 60870-5-104 PROTOCOL D.4 IEC 104 SETTINGS
GEK-106310-AF F650 DIGITAL BAY CONTROLLER d-3
D.4 IEC 104 settings
The Communication settings for IEC 60870-5-104 protocol are the following:
Product Setup > Communication Settings > IEC 870-5-104
Name Value Units Range
Function DISABLED
TCP Port 2404 [0:65535]
Common Addr of ASDU 255 [0:65535]
Cyclic Meter Period 0 Seconds [0:3600]
Synchronization Event 0 Minutes [0:1400]
IEC104 NET1 CLI1 OCTET1 0 [0 : 255]
IEC104 NET1 CLI1 OCTET2 0 [0 : 255]
IEC104 NET1 CLI1 OCTET3 0 [0 : 255]
IEC104 NET1 CLI1 OCTET4 0 [0 : 255]
IEC104 NET1 CLI2 OCTET1 0 [0 : 255]
IEC104 NET1 CLI2 OCTET2 0 [0 : 255]
IEC104 NET1 CLI2 OCTET3 0 [0 : 255]
IEC104 NET1 CLI2 OCTET4 0 [0 : 255]
Function 2 DISABLED
TCP Port 2 2404 [0:65535]
Common Addr of ASDU 2 255 [0:65535]
IEC104 NET2 CLI1 OCTET1 0 0 : 255]
IEC104 NET2 CLI1 OCTET2 0 0 : 255]
IEC104 NET2 CLI1 OCTET3 0 0 : 255]
IEC104 NET2 CLI1 OCTET4 0 0 : 255]
IEC104 NET2 CLI2 OCTET1 0 0 : 255]
IEC104 NET2 CLI2 OCTET2 0 0 : 255]
IEC104 NET2 CLI2 OCTET3 0 0 : 255]
IEC104 NET2 CLI2 OCTET4 0 0 : 255]
IEC104 SCALE CURRENT 1
IEC104 SCALE VOLTAGE 1
IEC104 SCALE POWER 1
IEC104 SCALE ENERGY 1
IEC104 SCALE OTHER 1
IEC104 DEADBAND CURRENT 30000 [0:65535]
IEC104 DEADBAND VOLTAGE 30000 [0:65535]
IEC104 DEADBAND POWER 30000 [0:65535]
IEC104 DEADBAND ENERGY 30000 [0:65535]
IEC104 DEADBAND OTHER 30000 [0:65535]
IEC104 IOA BINARIES 1000 [0:65535]
IEC104 IOA DOUBLE POINTS 1500 [0:65535]
IEC104 IOA ANALOGS 2000 [0:65535]
IEC104 IOA COUNTERS 4000 [0:65535]
IEC104 IOA COMMANDS 3000 [0:65535]
IEC104 IOA ANALOG
PARAMETERS
5000 [0:65535]