5-154 F650 DIGITAL BAY CONTROLLER GEK-106310-AF
5.7 REMOTE COMMS CHAPTER 5: SETPOINTS
5.7 Remote comms
This settings allow configuring the remote comms settings for the IEC61850 protocol regarding GSSE. For more
information see 7.2 IEC 61850 profile for F650.
SETPOINT > INPUTS/OUTPUTS > REMOTE COMMS
SETTING DESCRIPTION NAME DEFAULT VALUE STEP RANGE
Remote comms selection Remote Comms NONE N/A
[NONE – GSSE – GOOSE]
SETTING DESCRIPTION FOR GSSE
Remote comms selection Remote Comms GSSE N/A [NONE – GSSE – GOOSE]
Device Identification 650 ID F650 N/A
Hold time signal send by the
tra
nsmitting device
Hold Time 10000 1 ms [1000 : 60000]
Snapshot Events Generation Snapshot Events Remote Out DISABLED N/A [DISABLED – ENABLED]
Remote Device Description Remote Device X Remote Device X N/A
Bit Pair Selection Bit Pair X None N/A [DNA-1 to DNA-32 – UserSt-
1 t
o UserSt-64]
Default Value Selection Default Value X OFF N/A
[OFF – ON – LATEST OFF –
LATEST ON]
SETTING DESCRIPTION FOR GOOSE
Remote comms selection Remote Comms GOOSE N/A [NONE – GSSE – GOOSE]
Default Value Selection Default Value X OFF N/A [OFF – ON – LATEST OFF –
LA
TEST ON]
Note: X is the Remote Device index, up to 32