2-20 F650 DIGITAL BAY CONTROLLER GEK-106310-AF
2.5 TECHNICAL SPECIFICATIONS CHAPTER 2: PRODUCT DESCRIPTION
SNAPSHOT EVENTS
Capacity*: ....................................................................................1023 scrolling events
Time-tag:......................................................................................1 ms using an internal clock of 100 μs
Timing Accuracy: .....................................................................1 ms (using IRIG-B synchronization)
Triggers: ........................................................................................any element pickup, dropout, or operation
digital input/output change of state
virtual inputs and control events
Data Storage: .............................................................................non-volatile (flash) memory without battery
*Note: For firmware 7.20, up to 511 snapshot events are available. For firmware below 7.20, up to 479 snapshot events are available.
CONTROL EVENTS
Capacity: ......................................................................................128 events programmable through PLC
Time-tag:......................................................................................1 ms plus one PLC cycle using an internal clock of 100 μs. For
digital inputs,
the debounce time of these digital inputs must be added.
Timing Accuracy: .....................................................................1 ms (with IRIG-B synchronization input)
Trigger: ..........................................................................................Any digital signal programmable through the PLC
Alarm:.............................................................................................Control events can be displayed as an alarm on the alarms panel. Information is
alw
ays available through Communications for all models and in the HMI for models
with a graphical display (M in order code).
Data Storage: .............................................................................non-volatile (flash) memory without battery
Control events are also displayed in the snapshot events recording
DEMAND
Channels:......................................................................................9
Parameters:.................................................................................Ia (kA RMS), Ib (kA RMS), Ic (kA RMS), Ig (kA RMS), Isg (kA RMS), I2 (kA), P (MW), Q (MVAr)
and S (MV
A)
Current and Power Method:................................................Thermal Exponential, Block Interval, Rolling Demand
Measurements:..........................................................................Each channel shows the present and maximum measured value, with date and time
f
or the maximum recorded value.
Samples: .......................................................................................5, 10, 15, 20, 30, 60 minutes
Accuracy: .....................................................................................±2%
Trigger Input: ..............................................................................selectable by setting (operation mode selection for the block interval calculation
method
)
Snapshot Events:......................................................................selectable by setting
DATA LOGGER
Number of Channels:..............................................................1 to 16
Parameters:.................................................................................any available analog actual value
Samples: .......................................................................................1 second, 1, 5, 10, 15, 20, 30, 60 minutes
Storage Capacity:.....................................................................fixed, 32768 measurements