APPENDIX C: DNP 3.0 PROTOCOL FOR F650 C.2 DNP 3.0 DEVICE PROFILE DOCUMENT
GEK-106310-AF F650 DIGITAL BAY CONTROLLER c-7
DNP V3.00 DEVICE PROFILE DOCUMENT (Sheet 3 of 3)
Reports Binary Input Change Events when no specific
variation requested:
Never
Only time-tagged
Only non-time-tagged
Configurable
Reports time-tagged Binary Input Change Events when no
specific variation requested:
Never
Binary Input Change With Time
Binary Input Change With Relative Time
Configurable (attach explanation)
Sends Unsolicited Responses:
Never
Configurable
Only certain objects
Sometimes (attach explanation)
ENABLE/DISABLE unsolicited Function codes
supported
Sends Static Data in Unsolicited Responses:
Never
When Device Restarts
When Status Flag Change
No other options permitted
Explanation of ‘Sometimes’: It will be disabled for RS-
485 applications, since there is no collision avoidance
mechanism. For ethernet communication it will be
available and it can be disabled or enabled with the
proper function code.
Default CounterObject/Variation:
No Counters Reported
Configurable (attach explanation)
Default Object: 20.
Default Variation: 1
Point-by-point list attached
Counters Roll Over at:
No Counters Reported
Configurable (attach explanation)
16 Bits
32 Bits
Other Value: ______
Point-by-point list attached
Sends Multi-Fragment Responses:
Yes
No