ID 442426.04 100WE KEEP THINGS MOVING
Connection
7
Manual SD6
Connection without output derater
Observe the following points when connecting the motor without the output
derater:
Ground the shield of the motor cable with the shield connection clamp on
the EMC shroud.
Keep the exposed conductor as short as possible. All devices and circuits
that are sensitive to EMC must be kept at a distance of at least 0.3 m.
Connection with output derater
Observe the following points when connecting the motor to the output derater:
Ground the shield of the motor cable with large area contacts in the
immediate vicinity of the output derater, for example with electrically
conductive metal cable terminals on a grounded connection rail.
Keep the exposed conductor as short as possible. All devices and circuits
that are sensitive to EMC must be kept at a distance of at least 0.3 m.
The graphic below shows an example for the shielded connection of a motor
with output derater (graphic: icotek GmbH).
Pin 7 and
8 are
bridged at
the output
derator
1U1 1U2 1V1 1V2
1W1
1W2
7
PE
8
PE